logo
Jiangsu Changyun Intelligent Technology Co., Ltd
18706126999

GCK,GCS,MNS Series Low Voltage Draw-out Switchgear

GCK,GCS,MNS Series Low Voltage Draw-out Switchgear
Place of Origin:China
Brand Name:ChangYun
Certification:GB7251.1、ZBK36001、IEC439
Model Number:GCK,GCS,MNS
Product Details
Rated Insulation Voltage (V): 660 / 1000
Rated Operating Voltage (V): AC380 / AC660
Rated Frequency (Hz): 50 / 60
Overall Dimensions (Width×Depth×Height, Mm): 600(800)×1000×2200 / 800×1000×2200
Enclosure Protection Class: IP30 / IP40
Rated Current Of Horizontal Busbar (A): 1250 / 1600 / 2000 / 2500 / 3200 / 4000
Product Description
Detailed Specifications & Features

Low-Voltage Draw-Out Switchgear

Modular | Safe | Intelligent | IEC/GB Compliant

Overview

This low-voltage withdrawable switchgear (MCC) is designed for power distribution and motor control in industrial, commercial, and infrastructure projects. The drawer units adopt a standardized modular architecture supporting live hot-swap replacement, minimizing system downtime. Mechanical interlocks enforce three distinct positions – Connected, Test, and Disconnected – enabling isolated maintenance of faulty circuits without a full power shutdown.


Key Technical Features

1. Draw-Out Mechanism with Positive Interlocking

  • Three-position drawer: Connected (power circuit closed), Test (control circuit closed, main circuit isolated), Disconnected (fully isolated).

  • Mechanical interlock between drawer operating handle and compartment door: door can only be opened when handle is in Disconnected position.

  • Interchangeable drawer units of same rating – no special adjustment required for replacement or expansion.

2. Robust Construction & Material Standards

  • GCK series: Compact, cost-effective, widely used in general industrial distribution.

  • GCS series: High-strength section steel frame, deeper drawer compartments, able to accommodate higher-rated components (e.g., 630A and above); superior short-circuit withstand capacity (up to 100kA).

  • MNS series: C-section steel framework (forming a self-supporting structure), high circuit density (up to 36 circuits per cubicle), supports double-sided operation for space-constrained E-house applications.

3. Compartment Segregation & Arc Protection

  • Physically separated compartments: Busbar compartment (top), Electrical compartment (front), Cable compartment (rear/bottom). Separators are made of steel or flame-retardant insulating plates.

  • Busbars are covered with flame-retardant insulating sleeves or shields to mitigate arc-flash risks.

  • Protection rating: IP30 / IP40 (selectable), preventing ingress of solid foreign objects ≥2.5mm or ≥1.0mm.

4. Safety Interlocks & Misoperation Prevention

  • Drawer mechanical interlock (prevents moving between positions unless handle is correctly operated)

  • Door interlock (door locked when drawer is in Connected or Test position)

  • Anti-misoperation shutter mechanism (automatically covers live fixed contacts when drawer is withdrawn)

5. Intelligent & Expandable Architecture

  • Reserved slots for intelligent monitoring modules (current, voltage, power, temperature, contactor status).

  • Supports three-remote functions  – remote signaling, remote measurement, remote control – for integration into SCADA or power automation systems.

  • Optional communication protocols: Modbus RTU, Profibus, IEC 61850 (upon request).

  • Compatible with mainstream low-voltage components (ACB, MCCB, contactors, soft starters, VFDs) from ABB, Schneider, CHINT, etc.

  • Custom engineering available: special copper layouts, N+1 redundancy, form of internal separation (Form 3b/4b).

6. Standardized & Flexible Configuration

  • Standardized modular hole patterns for mounting devices – strong universality of auxiliary components.

  • Mixed configuration: withdrawable drawers and fixed compartments can be combined within the same cabinet.

  • Top-mounted busbar bridge optional for top or bottom cable entry/exit.


Technical Specifications (Typical)

Parameter Value
Rated insulation voltage (Ui) 690V / 1000V (optional)
Rated operational voltage (Ue) 380V, 400V, 415V, 690V
Rated impulse withstand voltage (Uimp) 8kV / 12kV
Rated frequency 50/60Hz
Rated short-time withstand current (Icw) 50kA / 80kA / 100kA (1s)
Rated peak withstand current (Ipk) 105kA – 220kA
Protection degree IP30, IP40 (IP54 available with special enclosure)
Drawer height module 8E/4, 8E/2, 8E, 16E, 24E (MNS/GCS based)
Max. number of drawers per cubicle 18 (depending on rating)
Applicable standards IEC 61439-1/2, GB/T 7251.8, GB/T 7251.12

Application Scenarios

  • Industrial plants (steel, chemical, cement, automotive)

  • Commercial buildings and data centers

  • Renewable energy projects (PV combiner boxes, wind power auxiliary systems)

  • Infrastructure (tunnels, water treatment, airports, metro stations)

  • Smart factory retrofit with digital O&M backend (real-time temperature/vibration/breaker status monitoring)


Why This Product?

  • Maximized uptime – Hot-swappable drawers reduce MTTR (Mean Time To Repair) from hours to minutes.

  • Engineered safety – Three-position interlock + compartment segregation meets highest safety requirements for live working.

  • Scalable – Add or upgrade circuits without changing the main cabinet.

  • Global compatibility – Works with major OEM components, certified to international standards.


Typical Applications

  • Low-voltage power distribution and motor control centers (MCC) in industrial facilities

  • Low-voltage distribution systems for data centers and commercial buildings

  • Critical load distribution in metallurgy, petrochemical, and power industries

  • Automated production lines requiring high reliability and maintainability


Contact our engineering team for a configuration drawing, short-circuit calculation, or a customized quotation.

Message for quick reply